- Adjustable and pre-set relative humidity
- Status indicator (LED)
- High switching capacity
- Clip fixing
- Temperature-compensated
The electronic hygrostat senses the relative humidity in an enclosure with electric/electronic components and turns on a heater at the set point, helping prevent the formation of condensation in the enclosure. The LED integrated in the adjustment knob is lit when the connected heater is in operation.
Switch difference | 5% RH (±3% RH tolerance) at +25°C (+77°F), 50% RH |
---|---|
Reaction time | 5 sec. |
Contact type | change-over contact (relay) |
Service life | > 50,000 cycles |
Max. switching capacity (relay output) | 240VAC / 120VAC 8 (1.6) A DC 100W at 24VDC |
Max. inrush current | AC 16A for 10 sec. |
Optical indicator | LED |
Connection | 5-pole terminal, clamping torque 0.5Nm max.: rigid/stranded1 wire 2.5mm² (AWG 14) |
Mounting | clip for 35mm DIN rail, EN 60715 |
Casing | plastic according to UL94 V-0, light grey |
Dimensions | 64.5 x 42 x 38mm |
Weight | approx. 70g |
Fitting position | vertical |
Operating/Storage temperature | 0 to +60°C (+32 to +140°F) / -20 to +70°C (-4 to +158°F) |
Operating/Storage humidity | max. 90% RH (non-condensing) |
Protection type | IP20 |
¹ When connecting with stranded wires, wire end ferrules must be used.
Art. No. | Operating voltage | Setting range | Approvals | ||
---|---|---|---|---|---|
01245.0-00 | 230VAC, 50/60Hz | 40 to 90% RH | VDE | UL File No. E164102 | EAC |
01246.0-00 | 230VAC, 50/60Hz | 65% RH pre-set | VDE | UL File No. E164102 | EAC |
01246.0-01 | 230VAC, 50/60Hz | 50% RH pre-set | VDE | UL File No. E164102 | EAC |
01245.9-00 | 120VAC, 50/60Hz | 40 to 90% RH | - | UL File No. E164102 | EAC |
01246.9-00 | 120VAC, 50/60Hz | 65% RH pre-set | - | UL File No. E164102 | EAC |
Technical drawing
- www.stego.ru>
- Products>
- Regulating>
- Regulators>
- EFR 012 | Electronic Hygrostat